Section 4
Protection functions
286
I_A
Level
I_B
detector
I_C
BLOCK
GUID-93025A7F-12BE-4ACD-8BD3-C144CB73F65A-ANSI V2 EN
Figure 136:
Functional module diagram
Level detector
The measured phase currents are compared to the set Pickup value. The TRMS values of
the phase currents are considered for the level detection. The timer module is enabled if
at least two of the measured phase currents exceed the set Pickup value.
Timer
Once activated, the internal PICKUP signal is activated. The value is available only
through the Monitored data view. The time characteristic is according to DT. When the
operation timer has reached the Trip delay time value, the TRIP output is activated.
When the timer has elapsed but the motor stall condition still exists, the TRIP output
remains active until the phase currents values drop below the Pickup value, that is, until
the stall condition persists. If the drop-off situation occurs while the trip time is still
counting, the reset timer is activated. If the drop-off time exceeds the set Reset delay time,
the operation timer is reset.
The timer calculates the pickup duration value PICKUP_DUR, which indicates the
percentage ratio of the pickup situation and the set trip time. The value is available in the
monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the BLOCK input and the global setting Configuration/System/Blocking
mode which selects the blocking mode. The BLOCK input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the BLOCK signal activation is preselected with the global
setting Blocking mode.
The Blocking mode setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block TRIP output" mode, the function
operates normally but the TRIP output is not activated.
TIMER
TRIP
t
Blocking
logic
1MAC059074-MB A
615 series ANSI
Technical Manual