1MAC059074-MB A
4.2.1.7
4.2.1.8
615 series ANSI
Technical Manual
The Type of reset curve setting does not apply to 50N-3, 50G-3 or when
the DT operation is selected. The reset is purely defined by the Reset delay
time setting.
Application
51N, 51G, 50N, 50G, 50N-3, 50G-3 is designed for protection and clearance of ground
faults in distribution and sub-transmission networks where the neutral point is isolated or
grounded via a resonance coil or through low resistance. It also applies to solidly grounded
networks and ground-fault protection of different equipment connected to the power
systems, such as shunt capacitor bank or shunt reactors and for backup ground-fault
protection of power transformers.
Many applications require several steps using different current pickup levels and time
delays. 51N, 51G, 50N, 50G, 50N-3, 50G-3 consists of three different protection stages:
•
Low 51N, 51G
•
High 50N, 50G
•
Instantaneous 50N-3, 50G-3
51N, 51G contains several types of time-delay characteristics. 50N, 50G and 50N-3,
50G-3 are used for fast clearance of serious ground faults.
Signals
Table 321:
51N,51G Input signals
Name
Type
IG
SIGNAL
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
Table 322:
50N,50G Input signals
Name
Type
IG
SIGNAL
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
Default
Description
0
Ground current
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
Default
Description
0
Ground current
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
Section 4
Protection functions
319