Parameter
Values (Range)
Ng Seq A low low Lim
0.00...40.00
Ng Seq A deadband
100...100000
Zro A Hi high Lim
0.00...40.00
Zro A High limit
0.00...40.00
Zro A low limit
0.00...40.00
Zro A low low Lim
0.00...40.00
Zro A deadband
100...100000
8.1.9.5
922
Unit
Step
xIn
1
1
xIn
1
xIn
1
xIn
1
xIn
1
1

Monitored data

Table 830:
I1,I2,I0 Monitored data
Name
Type
I2-A
FLOAT32
I1-A
FLOAT32
I0-A
FLOAT32
I2_INST
FLOAT32
I2_ANGL
FLOAT32
I2_DB
FLOAT32
I2_RANGE
Enum
I1_INST
FLOAT32
I1_ANGL
FLOAT32
Table continues on next page
Default
Description
0.00
Low alarm current limit for negative sequence
current
2500
Deadband configuration value for negative
sequence current for integral calculation.
(percentage of difference between min and
max as 0,001 % s)
0.20
High alarm current limit for zero sequence
current
0.05
High warning current limit for zero sequence
current
0.00
Low warning current limit for zero sequence
current
0.00
Low alarm current limit for zero sequence
current
2500
Deadband configuration value for zero
sequence current for integral calculation.
(percentage of difference between min and
max as 0,001 % s)
Values (Range)
Unit
0.00...40.00
xIn
0.00...40.00
xIn
0.00...40.00
xIn
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...40.00
xIn
-180.00...180.00
deg
1MAC059074-MB A
Description
Measured negative sequence
current
Measured positive sequence
current
Measured zero sequence
current
Negative sequence current
amplitude, instantaneous
value
Negative sequence current
angle
Negative sequence current
amplitude, reported value
Negative sequence current
amplitude range
Positive sequence current
amplitude, instantaneous
value
Positive sequence current
angle
615 series ANSI
Technical Manual