particular rotation direction, the reversed rotation direction can lead to an inefficient
cooling of the motor due to the fan design.
In a motor, the value of the negative-sequence component of the phase currents is very
negligible when compared to the positive-sequence component of the current during a
healthy operating condition of the motor. But when the motor is started with the phase
connections in the reverse order, the magnitude of I
of I
exceeds the pickup value, the function detects the reverse rotation direction and
2
provides an operating signal that disconnects the motor from the supply.

Signals

Table 495:
46R Input signals
Name
Type
I
SIGNAL
2
BLOCK
BOOLEAN
Table 496:
46R Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
xIn
0.01
ms
10
Unit
Step
is very high. So whenever the value
2
Default
Description
0
Negative sequence current
0=False
Block signal for activating the blocking mode
Description
Trip
Pickup
Default
Description
0.75
Pickup value
100
Trip delay time
Default
Description
1=enable
Operation Disable / Enable