The frequent operation counter limit is reached and new sequence is initiated. The
lockout is released when the recovery timer elapses.
The protection trip signal has been active longer than the time set with the Max wait
time parameter since the shot initiation.
The circuit breaker is closed manually during an autoreclosing sequence and the
manual close mode is FALSE.

Protection coordination controller

The PROT_CRD output is used for controlling the protection functions. In several
applications, such as fuse-saving applications involving down-stream fuses, tripping and
initiation of shot 1 should be fast (instantaneous or short-time delayed). The tripping and
initiation of shots 2, 3 and definite tripping time should be delayed.
In this example, two overcurrent elements 51P and 50P-2 are used. 50P-2 is given an
instantaneous characteristic and 51P is given a time delay.
The PROT_CRD output is activated, if the SHOT_PTR value is same or higher than the
value defined with the Protection crd limit setting and all initialization signals have been
reset. The PROT_CRD output is reset under the following conditions:
If the cut-out time elapses
If the reclaim time elapses and the AR function is ready for a new sequence
If the AR function is in lockout or disabled, that is, if the value of the Protection crd
mode setting is "AR inoperative" or "AR inop, CB man".
The PROT_CRD output can also be controlled with the Protection crd mode setting. The
setting has the following modes:
"no condition": the PROT_CRD output is controlled only with the Protection crd limit
setting
"AR inoperative": the PROT_CRD output is active, if the AR function is disabled or
in the lockout state, or if the INHIBIT_RECL input is active
"CB close manual": the PROT_CRD output is active for the reclaim time if the circuit
breaker has been manually closed, that is, the AR function has not issued a close
command
"AR inop, CB man": both the modes "AR inoperative" and "CB close manual" are
effective
"always": the PROT_CRD output is constantly active
1MAC059074-MB A
615 series ANSI
Technical Manual