Section 4
Protection functions
468
GUID-74289FF5-E90D-4633-9FEE-04DB8E86A3AE V1 EN
Figure 227:
Example of CT ratio correction setting calculation with in-zone
transformer
The rated load of the transformer is:
HV side (A): I
= 5 MVA / (1.732 × 20 kV) = 144.3 A
nT_A
LV side (A): I
= 5 MVA / (1.732 × 10.5 kV) = 274.9 A
nT_B
So the settings for CT ratio Corrections at HV (A) and LV (B) side are:
CT ratio Correction (A) = 200 A / 144.3 A = 1.386
CT ratio Correction (B) = 300 A / 274.9 A = 1.091
CT connections
The connections of the primary current transformers are designated as "Type 1" and
"Type 2".
If the positive directions of the winding 1 and winding 2 protection relay currents are
opposite, the CT connection type setting parameter is "Type 1". The connection
examples of "Type 1" are as shown in the
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the CT connection type setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in the
The default value of the CT connection type setting is "Type 1".
Figure 228
and
Figure
229.
Figure 230
and
Figure
231.
1MAC059074-MB A
615 series ANSI
Technical Manual