615 series ANSI
Technical Manual

Technical data

Table 762:
MCS-A, MCS-B, MCS-C Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Retardation time
Trip time accuracy in definite time mode
Technical revision history
Table 763:
MCS-A, MCS-B, MCS-C Technical revision history
Technical revision
B
Protection communication supervision PCS
Identification
Function description
Protection communication supervision
Function block
PCS
OK
WARNING
ALARM
COMM
GUID-DCE29B59-34C4-4FF9-9B6C-76BE2AEDBF31 V1 EN
Figure 444:
Function block
Supervision functions
Value
Depending on the frequency of the current
measured: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
<40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
Change
Function name changed from HZCCRDIF to
HZCCASPVC, HZCCBSPVC, HZCCCSPVC.
IEC 61850
IEC 60617
identification
identification
PCSITPC
PCS
Section 6
n
ANSI/IEEE C37.2
device number
PCS
861