Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
8.1.7.4
Table 817:
VG Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
V Hi high limit res
0.00...4.00
V high limit res
0.00...4.00
V deadband res
100...100000
Table 818:
VG Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
1=RMS
2=DFT
8.1.7.5
615 series ANSI
Technical Manual

Settings

Unit
Step
xUn
1
xUn
1
1
Unit
Step
Monitored data
Table 819:
VG Monitored data
Name
Type
VG-kV
FLOAT32
BLOCK
BOOLEAN
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
VG_INST
FLOAT32
VG_ANGL
FLOAT32
VG_DB
FLOAT32
VG_DMD
FLOAT32
VG_RANGE
Enum
Measurement functions
Default
Description
1=enable
Operation Disable / Enable
0.20
High alarm voltage limit
0.05
High warning voltage limit
10000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Default
Description
2=DFT
Selects used measurement mode
Values (Range)
Unit
0.00...4.00
xUn
0=False
1=True
0=False
1=True
0=False
1=True
0.00...4.00
xUn
-180.00...180.00
deg
0.00...4.00
xUn
0.00...4.00
xUn
0=normal
1=high
2=low
3=high-high
4=low-low
Section 8
Description
Measured residual voltage
Block signal for all binary
outputs
High alarm
High warning
Ground voltage Amplitude,
magnitude of instantaneous
value
Residual voltage angle
Ground voltage Amplitude,
magnitude of reported value
Demand value of residual
voltage
Ground voltage Amplitude
range
917

Advertisement

Table of Contents
loading