Section 4
Protection functions
Parameter
Values (Range)
Operating curve type
1=ANSI Ext Inv
3=ANSI Norm Inv
5=ANSI DT
9=IEC Norm Inv
10=IEC Very Inv
12=IEC Ext Inv
15=IEC DT
17=Programmable
Trip delay time
40...200000
Characteristic angle
-179...180
Max forward angle
0...90
Max reverse angle
0...90
Min forward angle
0...90
Min reverse angle
0...90
Table 251:
67/50P Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Voltage Mem time
0...3000
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
Table 252:
67/50P Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
254
Unit
Step
Default
15=IEC DT
ms
10
40
deg
1
60
deg
1
80
deg
1
80
deg
1
80
deg
1
80
Unit
Step
Default
1=Immediate
ms
1
40
5=Cross pol
Unit
Step
Default
1=enable
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
1=1 out of 3
1MAC059074-MB A
Description
Selection of time delay curve type
Trip delay time
Characteristic angle
Maximum phase angle in forward direction
Maximum phase angle in reverse direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Description
Selection of reset curve type
Voltage memory time
Reference quantity used to determine fault
direction
Description
Operation Disable / Enable
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Number of phases required for trip activation