Section 4
Protection functions
4.7.2.7
Table 608:
40 Group settings (Basic)
Parameter
Values (Range)
Diameter
1...6000
Offset
-1000...1000
Displacement
-1000...1000
Trip delay time
60...200000
Table 609:
40 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
External Los Det Ena
0=Disable
1=Enable
Voltage reversal
0=No
1=Yes
Impedance Meas mode
1=1Phase-to-earth
2=1Phase-to-
phase
3=3Phase-to-earth
4=3Phase-to-
phase
5=Pos sequence
Phase Sel for Z Clc
1=A or AB
2=B or BC
3=C or CA
Table 610:
40 Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
704
Table 607:
40 Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
%Zn
1
%Zn
1
%Zn
1
ms
10
Unit
Step
Unit
Step
ms
10
Description
Trip
Pickup
Default
Description
200
Diameter of the Mho diagram
-10
Offset of top of the impedance circle from the
R-axis
0
Displacement of impedance circle centre from
the X-axis
5000
Trip delay time
Default
Description
1=enable
Operation Disable / Enable
1=Enable
Enable external excitation loss detection
0=No
Rotate voltage signals by 180 degrees
5=Pos sequence
Select voltage and currents for impedance
calculation
1=A or AB
Voltage phase selection
Default
Description
3000
Reset delay time
1MAC059074-MB A
615 series ANSI
Technical Manual