Section 3 Basic Functions; General Parameters - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Section 3
3.1
Table 5:
Analog input settings, phase currents
Parameter
Values (Range)
Primary current
1.0...6000.0
Secondary current
2=1A
3=5A
Amplitude corr. A
0.9000...1.1000
Amplitude corr. B
0.9000...1.1000
Amplitude corr. C
0.9000...1.1000
39...4000
1)
Nominal Current
1.000...150.000
1)
Rated secondary Val
Reverse polarity
0=False
1=True
Angle Corr A
-20.0000...20.0000
Angle Corr B
-20.0000...20.0000
Angle Corr C
-20.0000...20.0000
1) Available for sensor analog inputs only
Table 6:
Analog input settings, residual current
Parameter
Values (Range)
Primary current
1.0...6000.0
Secondary current
1=0.2A
2=1A
3=5A
Amplitude corr.
0.9000...1.1000
Reverse polarity
0=False
1=True
Angle correction
-20.0000...20.0000
615 series ANSI
Technical Manual
Basic functions

General parameters

Unit
Step
A
0.1
0.0001
0.0001
0.0001
A
1
mV/Hz
0.001
deg
0.0001
deg
0.0001
deg
0.0001
Unit
Step
A
0.1
0.0001
deg
0.0001
Default
Description
100.0
Rated primary current
2=1A
Rated secondary current
1.0000
Phase A amplitude correction factor
1.0000
Phase B amplitude correction factor
1.0000
Phase C amplitude correction factor
1300
Network Nominal Current (In)
3.000
Rated Secondary Value (RSV) ratio
0=False
Reverse the polarity of the phase CTs
0.0000
Phase A angle correction factor
0.0000
Phase B angle correction factor
0.0000
Phase C angle correction factor
Default
Description
100.0
Primary current
2=1A
Secondary current
1.0000
Amplitude correction
0=False
Reverse the polarity of the residual CT
0.0000
Angle correction factor
Section 3
Basic functions
59

Advertisement

Table of Contents
loading