Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.5.1.8
Table 514:
59 Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.05...1.60
Time multiplier
0.05...15.00
Trip delay time
40...300000
Operating curve type
5=ANSI DT
15=IEC DT
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
Table 515:
59 Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
Type of time reset
1=Freeze Op timer
2=Decrease Op
timer
Table 516:
59 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Curve parameter A
0.005...200.000
Curve parameter B
0.50...100.00
Curve parameter C
0.0...1.0
Curve parameter D
0.000...60.000
Curve parameter E
0.000...3.000
Voltage selection
1=phase-to-earth
2=phase-to-phase
616

Settings

Unit
Step
xUn
0.01
0.01
ms
10
Unit
Step
Unit
Step
1
1
1
1
1
Default
Description
1.10
Pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
40
Trip delay time
15=IEC DT
Selection of time delay curve type
Default
Description
1=Immediate
Selection of reset curve type
1=Freeze Op timer
Selection of time reset
Default
Description
1=enable
Operation Disable / Enable
1=1 out of 3
Number of phases required for trip activation
1.000
Parameter A for customer programmable
curve
1.00
Parameter B for customer programmable
curve
0.0
Parameter C for customer programmable
curve
0.000
Parameter D for customer programmable
curve
1.000
Parameter E for customer programmable
curve
2=phase-to-phase
Parameter to select phase or phase-to-phase
voltages
1MAC059074-MB A
615 series ANSI
Technical Manual