Section 4
Protection functions
4.4.2.7
Table 489:
46PD Group settings (Basic)
Parameter
Values (Range)
Pickup value
10...100
Trip delay time
100...30000
Table 490:
46PD Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 491:
46PD Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Min phase current
0.05...0.30
4.4.2.8
4.4.2.9
598

Settings

Unit
Step
%
1
ms
1
Unit
Step
Unit
Step
ms
1
xIn
0.01
Monitored data
Table 492:
46PD Monitored data
Name
Type
PICKUP_DUR
FLOAT32
RATIO_I2_I1
FLOAT32
46PD
Enum
Technical data
Table 493:
46PD Technical data
Characteristic
Operation accuracy
Pickup time
Reset time
Table continues on next page
Default
Description
10
Pickup value
100
Trip delay time
Default
Description
1=enable
Operation Disable / Enable
Default
Description
20
Reset delay time
0.10
Minimum phase current
Values (Range)
Unit
0.00...100.00
%
0.00...999.99
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±2% of the set value
<70 ms
Typically 40 ms
1MAC059074-MB A
Description
Ratio of pickup time / trip time
Measured current ratio I2 / I1
Status
615 series ANSI
Technical Manual