ABB 615 series Technical Manual page 259

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Table 248:
67/51P Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 249:
67/51P Non group settings (Advanced)
Parameter
Values (Range)
Minimum trip time
20...60000
Reset delay time
0...60000
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Allow Non Dir
0=False
1=True
Min trip current
0.01...1.00
Min trip voltage
0.01...1.00
Table 250:
67/50P Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.10...40.00
Pickup value mult
0.8...10.0
Directional mode
1=Non-directional
2=Forward
3=Reverse
Time multiplier
0.05...15.00
Table continues on next page
615 series ANSI
Technical Manual
Unit
Step
Default
1=enable
1=1 out of 3
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
Unit
Step
Default
ms
1
20
ms
1
20
2=DFT
0=False
xIn
0.01
0.01
xUn
0.01
0.01
Unit
Step
Default
xIn
0.01
0.10
0.1
1.0
2=Forward
0.01
1.00
Protection functions
Description
Operation Disable / Enable
Number of phases required for trip activation
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum trip time for IDMT curves
Reset delay time
Selects used measurement mode
Allows prot activation as non-dir when dir info is
invalid
Minimum trip current
Minimum trip voltage
Description
Pickup value
Multiplier for scaling the pickup value
Directional mode
Time multiplier in IEC/ANSI IDMT curves
Section 4
253