Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Table 561:
24 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Cooling time
5...10000
Constant delay
100...120000
Maximum trip time
500000...10000000
Voltage selection
1=phase-to-earth
2=phase-to-phase
3=pos sequence
Phase selection
1=A or AB
2=B or BC
3=C or CA
Leakage React
0.0...50.0
Voltage Max Cont
80...160
Table 562:
24 Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Minimum trip time
200...60000
4.5.6.9
615 series ANSI
Technical Manual
Unit
Step
s
1
ms
10
ms
10
%
0.1
%
1
Unit
Step
ms
10
ms
10

Monitored data

Table 563:
24 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
T_ENARESTART
INT32
VOLTPERHZ
FLOAT32
24
Enum
Default
Description
1=enable
Operation Mode Disable/Enable
600
Time required to cool the machine
800
Parameter constant delay
1000000
Maximum trip time for IDMT curves
3=pos sequence
Selection of phase / phase-to-phase / pos
sequence voltages
1=A or AB
Parameter for phase selection
0.0
Leakage reactance of the machine
110
Maximum allowed continuous operating
voltage ratio
Default
Description
100
Resetting time of the trip time counter in DT
mode
200
Minimum trip time for IDMT curves
Values (Range)
Unit
0.00...100.00
%
0...10000
s
0.00...10.00
pu
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
Ratio of pickup time / trip time
(in %)
Estimated time to reset of
block restart
Excitation level, i.e U/f ratio or
Volts/Hertz
Status
657