Section 8
Measurement functions
8.2.2.4
8.2.2.5
940

Sampling frequencies

The sampling frequency of the disturbance recorder analog channels depends on the set
rated frequency. One fundamental cycle always contains the amount of samples set with
the Storage rate parameter. Since the states of the binary channels are sampled once per
task execution of the disturbance recorder, the sampling frequency of binary channels is
400 Hz at the rated frequency of 50 Hz and 480 Hz at the rated frequency of 60 Hz.
Table 848:
Sampling frequencies of the digital fault recorder analog channels
Storage rate
Recording length Sampling
(samples per
fundamental
cycle)
32
1* Record
length
16
2* Record
length
8
4 * Record
length
Uploading of recordings
The protection relay stores COMTRADE files to the C:\COMTRADE\ folder. The files
can be uploaded with the PCM600 or any appropriate computer software that can access
the C:\COMTRADE\ folder.
One complete disturbance recording consists of two COMTRADE file types: the
configuration file and the data file. The file name is the same for both file types. The
configuration file has .CFG and the data file .DAT as the file extension.
Sampling
frequency of
frequency of
analog channels,
binary channels,
when the rated
when the rated
frequency is 50
frequency is 50
Hz
Hz
1600 Hz
400 Hz
800 Hz
400 Hz
400 Hz
400 Hz
1MAC059074-MB A
Sampling
Sampling
frequency of
frequency of
analog channels,
binary channels,
when the rated
when the rated
frequency is 60
frequency is 60
Hz
Hz
1920 Hz
480 Hz
960 Hz
480 Hz
480 Hz
480 Hz