1MAC059074-MB A
4.3.1.6
615 series ANSI
Technical Manual
GUID-6F26D761-CB1D-4D86-80AA-CEC95CEBC1A9 V2 EN
Figure 238:
An example of a test mode situation where three-phase currents are
injected to the local end protection relay
GUID-21BCDEC5-2A22-4AEE-831E-BC8A72E40A64 V2 EN
Figure 239:
Local and remote end currents presented in a web HMI of the protection
relay
Application
87L is designed for the differential protection of overhead line and cable feeders in a
distribution network. 87L provides absolute selectivity and fast trip times as unit
protection also in short lines where distance protection cannot be applied.
Section 4
Protection functions
489