The voltage vector shift protection function 78V, also known as vector surge or delta phi
function, measures continuously the duration of a voltage cycle. At the instance of
islanding, the duration of measured voltage cycle becomes shorter or longer than the
previous one, that is, the measured voltage cycle shifts with time. This shifting of voltage
is measured in terms of phase angle. 78V issues an instantaneous trip when the shift in
voltage vector exceeds the set value.
The function can be blocked with BLOCK input. Blocking resets timers and outputs.
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of 78V can be described by using a module diagram. All the modules in the
diagram are explained in the next sections.
V_A_AB
Vector
V_B_BC
shift
detector
V_C_CA
BLOCK
GUID-7482410F-B8F0-4922-881C-F641139DBC5A V1 EN
Figure 334:
Functional module diagram
Vector shift detector
This module measures the duration of each cycle of the voltage signal phase. The duration
of the present cycle is compared to the previous cycle, considered as reference. When the
mains is lost, a sudden change is seen in the cycle length, if loading of the generator
changes suddenly and power mismatch or unbalance (generation vs. load) in the islanded
part of the network is large enough. The cycle shifts with time, that is, the frequency may
not change but a vector shift is seen in phase as shown in
This step is measured in degrees for each voltage signal defined by the Phase supervision
setting. The Phase supervision setting determines which voltage is used for detecting
vector shift. The available Phase supervision options are "All" and "Pos sequence". If the
calculated value of Δδ exceeds the set Pickup value setting for all the defined phases, the
module sends an enabling signal to start the Pulse timer.
The Voltage selection setting is used to select whether the available voltage signal is
phase-to-ground or phase-to-phase voltage.
Pulse timer
TRIP
INT_BLKD
Section 4
Protection functions
Figure
335.
667