Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
6.2.7
Table 742:
CCM Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Pickup value
0.05...0.20
Table 743:
CCM Non group settings (Advanced)
Parameter
Values (Range)
Max alarm current
1.00...5.00
6.2.8
6.2.9
6.2.10
615 series ANSI
Technical Manual

Settings

Unit
Step
xIn
0.01
Unit
Step
xIn
0.01
Monitored data
Table 744:
CCM Monitored data
Name
Type
I_DIFF
FLOAT32
CCM
Enum
Technical data
Table 745:
CCM Technical data
Characteristic
1)
Trip time
1) Including the delay of the output contact
Technical revision history
Table 746:
CCM Technical revision history
Technical revision
B
C
D
Default
Description
1=enable
Operation Enable / Disable
0.05
Minimum trip current differential level
Default
Description
1.50
Block of the function at high phase current
Values (Range)
Unit
0.00...40.00
xIn
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
<30 ms
Change
Internal improvement
Internal improvement
Internal improvement
Section 6
Supervision functions
Description
Differential current
Status
853