Section 3
Basic functions
Parameter
Values (Range)
Value maximum
-10000.0...10000.0
Value minimum
-10000.0...10000.0
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
3.13.5
128
Unit
Step
1
1
1
1
1
1
1

Monitored data

Table 60:
Monitored data
Name
Type
AI_DB1
FLOAT32
AI_RANGE1
Enum
AI_DB2
FLOAT32
AI_RANGE2
Enum
AI_DB3
FLOAT32
AI_RANGE3
Enum
AI_DB4
FLOAT32
AI_RANGE4
Enum
AI_DB5
FLOAT32
Table continues on next page
Default
Description
10000.0
Maximum output value for scaling and
supervision
-10000.0
Minimum output value for scaling and
supervision
10000.0
Output value high alarm limit for supervision
10000.0
Output value high warning limit for supervision
-10000.0
Output value low warning limit for supervision
-10000.0
Output value low alarm limit for supervision
1000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Values (Range)
Unit
-10000.0...10000
.0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000
.0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000
.0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000
.0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000
.0
1MAC059074-MB A
Description
mA input, Connectors 1-2,
reported value
mA input, Connectors 1-2,
range
mA input, Connectors 3-4,
reported value
mA input, Connectors 3-4,
range
RTD input, Connectors
5-6-11c, reported value
RTD input, Connectors
5-6-11c, range
RTD input, Connectors
7-8-11c, reported value
RTD input, Connectors
7-8-11c, range
RTD input, Connectors
9-10-11c, reported value
615 series ANSI