Signals

Table 201:
RCHLCCH output signals
Parameter
Values (Range)
CHLIV
True
False
REDCHLIV
True
False
LNKLIV
Up
Down
REDLNKLIV
Up
Down

Settings

Table 202:
Redundancy settings
Parameter
Values (Range) Unit
Redundant
None
mode
PRP
HSR

Monitored data

Monitored data is available in four locations.
Monitoring/Communication/Ethernet/Activity/CHLIV_A
Monitoring/Communication/Ethernet/Activity/REDCHLIV_B
Monitoring/Communication/Ethernet/Link statuses/LNKLIV_A
Monitoring/Communication/Ethernet/Link statuses/REDLNKLIV_B
Unit
Step
Default
Description
Status of redundant Ethernet channel
LAN A. When
"HSR" or "PRP", value is "True" if the
protection relay is receiving redundancy
supervision frames. Otherwise value is
"False".
Status of redundant Ethernet channel
LAN B. When
"HSR" or "PRP", value is "True" if the
protection relay is receiving redundancy
supervision frames. Otherwise value is
"False".
Link status of redundant port LAN A. Valid
only when
"HSR" or "PRP".
Link status of redundant port LAN B. Valid
only when
"HSR" or "PRP".
Step
Default
Description
None
Mode selection for Ethernet switch on
redundant communication modules. The
"None" mode is used with normal and Self-
healing Ethernet topologies.
Section 3
Basic functions
Redundant mode is set to
Redundant mode is set to
Redundant mode is set to
Redundant mode is set to