ABB 615 series Technical Manual page 315

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
615 series ANSI
Technical Manual
t/s
4000
3000
2000
x
1000
500
400
300
200
100
50
40
30
20
10
5
4
3
2
1.05
1
1
2
3
4
5
GUID-B6F9E655-4FFC-4B06-841A-68DADE785BF2 V1 EN
Figure 147:
The influence of Weighting factor p at prior load 1xFLC, timeconstant =
640 s, and Overload factor = 1.05
Setting the overload factor
The value of Overload factor defines the highest permissible continuous load. The
recommended value is 1.05.
Cold
curve
20
50
75
p
[%]
100
6
8
10
I/I
q
Section 4
Protection functions
309