Section 3
Basic functions
3.7.3
3.7.4
3.7.5
90
Behavior data objects in all logical nodes follow LD0.LLN0.Mod value.
If "Normal mode" is selected, behaviour data objects follow mode (.Mod)
data object of the corresponding logical device.
Vertical and horizontal communication is not blocked by the "IED
blocked" or "IED test and blocked" modes.

Application configuration and Test mode

The physical outputs from control commands to process are blocked with "IED blocked"
and "IED test and blocked" modes. If physical outputs need to be blocked from the
protection, the application configuration must be used to block these signals. Blocking
scheme needs to use BEH_BLK output of PROTECTION function block.

Control mode

The mode of all logical nodes located under CTRL logical device can be set with Control
mode. The Control mode parameter is available via the HMI or PCM600 path
Configuration/Control/General. By default, Control mode can only be set locally
through LHMI.Control mode inherits its value from Test mode but Control mode "On",
"Blocked" and "Off" can also be set independently. Control mode is also available via IEC
61850 communication (CTRL.LLN0.Mod).
Table 38:
Control mode
Control mode
On
Blocked
Off
Behavior data objects under CTRL logical device follow
CTRL.LLN0.Mod value. If "On" is selected, behavior data objects follow
the mode of the corresponding logical device.

Application configuration and Control mode

The physical outputs from commands to process are blocked with "Blocked" mode. If
physical outputs need to be blocked totally, meaning also commands from the binary
Description
Normal operation
Control function commands blocked
Control functions disabled
1MAC059074-MB A
Control BEH_BLK
FALSE
TRUE
FALSE
615 series ANSI
Technical Manual