Section 10
Power quality measurement functions
10.3.7
10.3.8
Table 930:
PQSS Group settings (Basic)
Parameter
Values (Range)
Reference voltage
10.0...200.0
Voltage dip set 1
10.0...100.0
VVa dip time 1
0.5...54.0
Voltage dip set 2
10.0...100.0
VVa dip time 2
10.0...180.0
Voltage dip set 3
10.0...100.0
VVa dip time 3
2000...60000
Voltage swell set 1
100.0...140.0
Table continues on next page
1056
Voltage variation measurement can be done to the phase-to-ground and phase-to-phase
voltages. The power quality standards do not specify whether the measurement should be
done to phase or phase-to-phase voltages. However, in some cases it is preferable to use
phase-to-ground voltages for measurement. The measurement mode is always TRMS.

Signals

Table 928:
PQSS Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
V_A
SIGNAL
V_B
SIGNAL
V_C
SIGNAL
BLOCK
BOOLEAN
Table 929:
PQSS Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
SWELLST
BOOLEAN
DIPST
BOOLEAN
INTST
BOOLEAN
Settings
Unit
Step
%Un
0.1
%
0.1
cycles
0.1
%
0.1
cycles
0.1
%
0.1
ms
10
%
0.1
Default
Description
0
Phase A current magnitude
0
Phase B current magnitude
0
Phase C current magnitude
0
Phase-to-ground voltage A
0
Phase-to-ground voltage B
0
Phase-to-ground voltage C
0=False
Block signal for activating the blocking mode
Description
Voltage variation detected
Voltage variation present
Voltage swell active
Voltage dip active
Voltage interruption active
Default
Description
57.7
Reference supply voltage in %
80.0
Dip limit 1 in % of reference voltage
3.0
Voltage variation dip duration 1
80.0
Dip limit 2 in % of reference voltage
30.0
Voltage variation dip duration 2
80.0
Dip limit 3 in % of reference voltage
3000
Voltage variation dip duration 3
120.0
Swell limit 1 in % of reference voltage
1MAC059074-MB A