Signals; Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.8.6
4.2.8.7
Table 417:
67YN Group settings (Basic)
Parameter
Values (Range)
Directional mode
2=Forward
3=Reverse
Voltage pickup value
0.01...1.00
Trip delay time
60...1200000
Table 418:
67YN Group settings (Advanced)
Parameter
Values (Range)
Operating quantity
1=Adaptive
2=Amplitude
Min trip current
0.005...5.000
Characteristic tilt angle
2.0...20.0
458
advantages of 67YN includes versatile applicability, good selectivity, good sensitivity
and easy setting principles.
One instance (stage) of 67YN function is available.

Signals

Table 415:
67YN Input signals
Name
Type
IG
SIGNAL
VG
SIGNAL
BLOCK
BOOLEAN
RELEASE
BOOLEAN
RESET
BOOLEAN
Table 416:
67YN Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLK_EF
BOOLEAN
INTR_EF
BOOLEAN
PEAK_IND
BOOLEAN

Settings

Unit
Step
xUn
0.01
ms
10
Unit
Step
xIn
0.001
deg
0.1
Default
Description
0
Residual current
0
Residual voltage
0=False
Block signal for activating the blocking mode
0=False
External trigger to release neutral admittance protection
0=False
External trigger to reset direction calculatio
Description
Trip
Pickup
Block signal for EF to indicate opposite direction peaks
Intermittent ground-fault indication
Current transient detection indication
Default
Description
2=Forward
Directional mode
0.10
Voltage pickup value
500
Trip delay time
Default
Description
1=Adaptive
Operating quantity selection
0.010
Minimum alarm current
5.0
Characteristic tilt angle
1MAC059074-MB A
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents