Measuring Modes - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 6
Supervision functions
6.3.5
6.3.6
856
Timer
The time characteristic is according to DT. When the alarm timer reaches the value set by
Alarm delay time, the ALARM output is activated. If the fault disappears before the module
generates an alarm signal, the reset timer is activated. If the reset timer reaches the value
set by Reset delay time, the alarm timer resets. The activation of the BLOCK signal resets
the Timer and deactivates the ALARM output.
Lockout logic
MCS-A, MCS-B, MCS-C is provided with the possibility to activate a lockout for the
ALARM output depending on the Alarm output mode setting. In the "Lockout" mode, the
ALARM must be reset manually from the LHMI Clear menu after checking the CT
secondary circuit. In the "Non-latched" mode, the ALARM output functions normally, that
is, it resets as soon as the fault is cleared.

Measuring modes

The function operates on two alternative measurement modes, DFT and Peak-to-Peak.
The measurement mode is selected using the Measurement mode setting.
Application
MCS-A, MCS-B, MCS-C is a dedicated phase-segregated supervision function to be used
along with the high-impedance differential protection for detecting the broken CT
secondary wires. The operation principle of MCS-A, MCS-B, MCS-C is similar to the
high-impedance differential protection function 87A, 87B, 87C. However, the current
setting of MCS-A, MCS-B, MCS-C is set to be much more sensitive than 87A, 87B, 87C
and it trips with a higher time delay. A typical example of the MCS-A, MCS-B, MCS-C
Pickup value setting is 0.1 pu with an Alarm delay time of 3 s or more.
As the current setting of MCS-A, MCS-B, MCS-C is more sensitive than the actual
differential stage, it can pick up internally under the through-fault conditions; however, a
sufficient time delay prevents false alarm. If the bus wire is broken, differential current
arises depending on the load of the feeder with the broken bus wire.
1MAC059074-MB A
615 series ANSI
Technical Manual