Signals; Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.2.7.6
4.2.7.7
Table 409:
27/59THN Group settings (Basic)
Parameter
Values (Range)
Beta
0.50...10.00
Voltage N 3.H Lim
0.005...0.200
Trip delay time
20...300000
615 series ANSI
Technical Manual
1.
For a particular value of Beta the third harmonic neutral voltage is measured with the
generator in the no-load condition and the circuit breaker in the closed position.
2.
With the same condition, the third harmonic neutral voltage with the circuit breaker
in the open position is measured.
3.
CB Open factor should be set equal to the ratio of the third harmonic neutral voltage
measured with the circuit breaker in the closed position to that in the open.

Signals

Table 407:
27/59THN Input signals
Name
Type
V_3H_A
SIGNAL
V_3H_B
SIGNAL
V_3H_C
SIGNAL
V_3H_N
SIGNAL
V_3H_RES
SIGNAL
BLOCK
BOOLEAN
GCB_CLOSED
BOOLEAN
Table 408:
27/59THN Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
INT_BLKD
BOOLEAN

Settings

Unit
Step
0.01
xUn
0.001
ms
10
Default
Description
0
Third harmonic of phase A voltage
0
Third harmonic of phase B voltage
0
Third harmonic of phase C voltage
0
Third harmonic of neutral voltage
0
Third harmonic of residual voltage
0=False
Block signal for activating the blocking mode
0=False
Generator CB in closed position
Description
Trip
Pickup
Protection internally blocked
Default
Description
3.00
Portion of neutral side 3rd harmonic used as
bias
0.010
Pickup value for 3rd harmonic residual
undervoltage protection
20
Trip delay time
Section 4
Protection functions
435