Section 4
Local HMI
4.3.3
4.3.4
74
Fig. 4.1
Local human-machine-interface (LHMI)

Protection Indicator LEDs

There are three LEDs on top of the display: green, yellow, and red.
Table 17
Local HMI Protection Indicator LEDs
LED
IEC label
ANSI label
green
Ready
Normal
yellow
Start
Pickup
red
Trip
Trip

LED signals

The local HMI contains 15 additional LEDs, each of which can be assigned to any
output signal and configured to latch or not to latch as required.
Refer to section 3.6.6 "HMI LEDs"
Description
Flashes while the system is being initialized. Continuously lit
during normal operation.
Not used.
Indicates a trip. Remains lit until applying a binary signal to the
reset input or selecting the HMI function "Reset latching".