H2: Digital Outputs - Omron Q2A Series Technical Manual

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Setting
Function
7F
Comms Test
90 to 97
Q2pack DI1 to 8
9F
Q2pack Disable
101 to 19F
Inverse Input of 1 to 9F

H2: DIGITAL OUTPUTS

No.
Name
(Hex.)
H2-01
2NO-2CM Func
Selection
(040B)
H2-02
3NO-3CM Func
Selection
(040C)
H2-03
4NO-4CM Funct
Selection
(040D)
H2-06
kWH Out Unit Selection
(0437)
H2-07
Mbus Reg1 Address
Select
(0B3A)
H2-08
Mbus Reg1 Bit Select
(0B3B)
H2-09
Mbus Reg2 Address
Select
(0B3C)
H2-10
Mbus Reg2 Bit Select
(0B3D)
H2-20
Compare1 Mon.
Selection
(1540)
H2-21
Compare1 Low Limit
(1541)
H2-22
Compare1 Up Limit
(1542)
H2-23
Compare1 Hysteresis
(1543)
H2-24
Compare1 On-Delay
Time
(1544)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Set the function for the drive to self-test RS-485 serial communications operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets digital inputs used with Q2pack. Refer to the Q2pack Online Manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the Q2pack program saved in the drive.
ON : Disabled
OFF : Enabled
Note:
Set A1-07 = 2 [Q2pack Enable = With DI] to use this function.
Sets the function of the selected MFDI to operate inversely. To select the function, enter "1xx", where the "xx" is
the function setting value.
Note:
You cannot use inverse input for all functions. Refer to
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFDO terminal 2NO-2CM.
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in
through mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFDO terminal 3NO-3CM.
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in
through mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for MFDO terminal 4NO-4CM.
Note:
Set this parameter to 0 when the terminal is not being used or to use the terminal in
through mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the unit for the output signal when H2-01 to H2-03 = 65 [xNO-xCM Func
Selection = WattH Pulse].
1 : 0.1 kWh units
2 : 1 kWh units
3 : 10 kWh units
4 : 100 kWh units
5 : 1000 kWh units
V/f
CL-V/f
OLV
CLV
AOLV
Sets the address of the Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bit of the Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the address of the Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bit of the Modbus register output to the MFDO terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [MONITOR].
For example, set x-xx to 102 to monitor U1-02 [Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit detection level for comparator 1 when the full scale analog output
for the monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit detection level for comparator 1 when the full scale analog output
for the monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the hysteresis level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Compare1 Mon.Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the on-delay time for comparator 1.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Table 12.40
for more information.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: TERMINALS
Ref.
687
687
687
688
Default
Ref.
(Range)
0
690
(0 - 1FF)
1
690
(0 - 1FF)
2
690
(0 - 1FF)
1
690
(1 - 5)
0001
691
(0001 - 1FFF)
0000
691
(0000 - FFFF)
0001
691
(0001 - 1FFF)
0000
691
(0000 - FFFF)
102
692
(000 - 999)
0.0%
692
(0.0 - 300.0%)
0.0%
692
(0.0 - 300.0%)
0.0%
692
(0.0 - 10.0%)
0.0 s
692
(0.0 - 600.0 s)
435
11