1-60
$Pn: 100 to 355
The results of communication with each station are stored here. The status codes are shown below.
Code (HEX)
0000H
Normal
FFFFH
Time-out
8001H
Check code error
8002H
Data error
800BH
Receives the error code from the connected device
Errors other than the above are stored as shown below.
MSB
15
14
13
Break detection
Error
0: Bits 0 to 14 are all "0".
1: Any bit from 0 to 14 is other than "0".
Error
Time-out
Check code
Data error
Error code received
Buffer full
Parity
Overrun
Framing
Break detection
 Solution
1) Check if the communication settings of the V9 series and the connected device are matched.
2) Check the cable connection.
3) Data may be disrupted because of noise. Fix noise.
If you still cannot solve the error even after following the solutions above, contact your local distributor.
12
11
10
9
8
7
0
0
0
Buffer-full error
Parity error
Overrun error
Framing error
Details
Although a request to send is given, no answer is
returned within the specified time.
The check code of the response is incorrect.
The code of the received data is invalid.
An error occurred on the connected device.
The V9 buffer is full.
An error occurred in parity check.
After receiving one character, the next character was
received before internal processing was completed.
Although the stop bit must be "1", it was detected as
"0".
The connected device's SD is remaining at the low
level.
Contents
LSB
6
5
4
3
2
1
0
0
0
0
0
0
0
0
Implement solutions 1, 2, and 3.
Implement solutions 1 and 3.
Implement solutions 1, 2, and 3.
Refer to the instruction manual for the PLC.
Contact your local distributor.
Implement solutions 2 and 3.
Implement solutions 1 and 3.
Implement solutions 1, 2, and 3.
Examine the connection with the connected device's
SD and RD.
Solution