13-22
13. OMRON
13.1.7 SYSMAC CS1/CJ1 DNA (Ethernet)
The V9 series can communicate with CS1/CJ1 on the network (Controller Link) via the Ethernet unit.
192.168.1.1
CJ1
ETN
Node
1
Network No. 5
Ethernet
V9
Node 10
192.168.1.10
Communication Setting
Editor
Make the following settings on the editor. For more information, see "1.3.2 Ethernet Communication".
 IP address for the V9 unit
- When specified on the screen program:
[System Setting]  [Hardware Setting]  [Local Port IP Address]
- When specified on the V9 unit:
Local mode  [LAN Setting]
 Port number (for communication with PLC) and local port number (V9 DNA table number) of the V9 unit
[System Setting]  [Hardware Setting]  [PLC Properties]  [Communication Setting]
192.168.1.2
CJ1
ETN
CLK
Node
Node
2
1
PLC table
SYSTEM
F 1
F 2
F 3
No.
IP address
F 4
F 5
0
F 6
F 7
1
192.168.1.1
2
192.168.1.2
:
The V9 series accesses to a PLC on the network number 1 or 2 via PLC table number
2 (192.168.1.2). In this case, specify "2" for the relay target.
CJ1
CLK
CJ1
Node
2
Network No. 1
DNA table
Network
No.
0
1
1
1
2
2
:
10
5
Set the network number and node number of the V9 to the
same DNA table number as the V9 node number.
CLK
CLK
CJ1
Node
Node
3
1
Network No. 2
Node
Relay target
2
2
3
2
2
2
10
0
Set the DNA table number of the V9.
Set the same number as the one
specified for [FINS/UDP Port] on
the PLC.
CLK
Node
2