*1
RS-485 communication is possible. Note that a communication fault (E.PUE) occurs as soon as the inverter is switched to the operation
mode with command source.
*2
When the value in the range from 0.1 to 999.8 is set:
If the V series does not start communication within the preset time, the inverter stops due to an alarm. This can be avoided by the
periodical reading setting.
*3
When the inverter is turned on with the settings of Pr.79=0/2/6 and Pr.340=1, the inverter enters in the Network operation mode.
*4
Operation mode can be changed between the PU operation mode and Network operation mode from the operation panel.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
P
(parameter)
D
(parameter)
D (Parameter)
Address
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
D10
D11
TYPE
00H
01H
Operation mode
Pr.37=0 : Frequency display, setting
Pr.370Machine speed at 60 Hz
Output current
Output voltage
Fault description (First fault in past / Latest fault)
Fault description (Third fault in past / Second fault in past)
Fault description (Fifth fault in past / Fourth fault in past)
Fault description (Seventh fault in past / Sixth fault in past)
Inverter status monitor
Bit
15
-
8
Not used
ABC (fault)*
FU (frequency detection)*
* Definitions change according to the Pr.190 to 192.
Second parameter changing
Special monitor
Special monitor selection No.
Data
Contents
H01
Output frequency / speed
H02
Output current
H03
Output voltage
H05
Frequency setting / speed setting
H07
Motor torque
H08
Converter output voltage
H09
Regenerative brake duty
Electric thermal relay function load
H0A
factor
H0B
Output current peak value
Converter output voltage peak
H0C
value
H0E
Output power
*1
H0F
Input terminal status
*1
Input terminal status
-
-
-
-
*2
Output terminal status
-
-
-
-
*3
Refer to the manual of the inverter.
9.2 Temperature Controller/Servo/Inverter Connection
Refer to the list file or the parameter list for the inverter.
Refer to the table below.
Name
0000 H: Network operation
0001 H: External operation
0002 H: PU operation
7
6
5
4
3
2
SU (Up-to-frequency)
OL (overload)
Unit
Data
0.01 Hz
H10
/ 0.001
0.01 A
H14
0.1V
H17
0.01 HZ
H18
/ 0.001
0.1 %
H19
0.1 V
H34
0.1 %
H35
0.1 %
H36
0.01 A
H3A
0.1 V
H3B
0.01 kW
H3C
-
-
RES
-
MRS
-
-
-
-
-
-
Remarks
1
0
Inverter running
(inverter running)*
Forward rotation (STF)
Reverse rotation (STR)
Contents
*2
Output terminal status
Cumulative energization time
Actual operating time
Motor load factor
Cumulative power
PID set point
PID measured value
PID deviation
*3
Option input terminal status1
*3
Option input terminal status2
Option output terminal status
RH
RM
RL
-
-
ABC
FU
-
9-73
Unit
-
1 h
1 h
0.1%
1 kWh
0.1 %
0.1 %
0.1 %
-
-
*3
-
-
STR
STF
-
-
RUN