Fuji Electric Monitouch V9 Series Connection Manual page 162

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

Parameter setting register
Register
0
0
R772
Response delay time
8
7
R773
Communication parameter settings can also be made by using the system parameter setting of the programmer. For more
information, refer to the PLC manual issued by the manufacturer.
Universal Communication Port 2
Set parameters into the special register "R774, 775", then set "A5AA" (HEX) into the setting complete register "R767". When
the set value at R767 is changed to "AAAA" (HEX), it is regarded as normal; if it is changed to "AEAA" (HEX), it is regarded as
erroneous.
Parameter setting register
Register
R774
Same as the setting register R772 for the universal port 1
R775
Same as the setting register R773 for the universal port 1
Communication parameter settings can also be made by using the system parameter setting of the programmer. For more
information, refer to the PLC manual issued by the manufacturer.
Universal Communication Port 3
Set parameters into the special register "R776, 777", then set "5AAA" (HEX) into the setting complete register "R767". When
the set value at R767 is changed to "AAAA" (HEX), it is regarded as normal; if it is changed to "EAAA" (HEX), it is regarded as
erroneous.
Parameter setting register
Register
R776
Same as the setting register R772 for the universal port 1
R777
Same as the setting register R773 for the universal port 1
Communication parameter settings can also be made by using the system parameter setting of the programmer. For more
information, refer to the PLC manual issued by the manufacturer.
Setting
E
0
Communication protocol
80: K-Sequence
E0: Automatic recognition (Modbus, CCM, K-Sequence)
Communication timeout
0: 800 ms
0: 0 ms
0
1
Station number
01 to 1F (HEX)
Baud rate
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
Parity stop bit
0: Without parity, stop bit 1
2: Without parity, stop bit 2
8: Odd parity, stop bit 1
A: Odd parity, stop bit 2
C: Even parity, stop bit 1
E: Even parity, stop bit 2
Setting
Setting
7.1 PLC Connection
(Underlined setting: default)
Setting Example
00E0H
K-Sequence
8701H
38400 bps
Odd parity
Stop bit 1
Station number 01
Setting Example
00E0H
8701H
Setting Example
00E0H
8701H
7-11