10-2
10. MODICON
10.1.1 Modbus RTU
Communication Setting
Editor
Communication setting
Item
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
PLC
Communication setting
ASCII
RTU
mem
Example: Station No. 1
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
4
(holding register)
3
(input register)
0
(output coil)
1
(input relay)
Notes on Creating Screen Programs
On the editor, the device memory address is specified in decimal notation. Thus, when the address of a connected device is
expressed in hexadecimal notation, convert the address into decimal one and add "1".
Switch
Setting
Communication
setting
SW1
Device address
1 to 64
SW2
Device Memory
Setting
1 to 247
Contents
RTU
9600 bps, 8 bits, 1 bit , even (fixed)
SW1
Station No.
(the tens
(1 to 64)
place)
1 to 9
0
10 to 19
1
20 to 29
2
30 to 39
3
40 to 49
4
50 to 59
5
60 to 64
6
TYPE
00H
01H
Read only
04H
06H
Read only
(Underlined setting: default)
Remarks
Remarks
When the communication setting
switch is set to "mem", the
parameters set in the PLC
SW2
programming software take
(the ones
effect.
place)
(Communication at 19200 bps
1 to 9
maximum is allowed.)
For more information, refer to
the PLC manual issued by the
manufacturer.
0 to 9
0 to 4
Remarks