Fuji Electric Monitouch V9 Series Connection Manual page 296

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

13.1.2 SYSMAC CV
Communication Setting
Editor
Communication setting
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Transmission Mode
Transmission mode 2
When the transmission mode 2 (BCD with signs) is selected, data in the PLC device memory can be displayed on MONITOUCH
as data with signs.
When higher 4 bits in the device memory indicates [F] or [A], it is treated as negative.
[F]:
Regards higher 4 bits as [0].
[A]:
Regards higher 4 bits as [1].
 Displayable range 1 word:
Example:
PLC Device Memory
00000000 to 99999999
F0000001 to F9999999
A0000000 to A9999999
 Setting procedure: Num. Display [Input Type: BCD]
PLC
CPU Unit
Communication selector switch
Communication Selector Switch
Item
1 : 1 / 1 : n / Multi-link2 / Multi-link2 (Ethernet) /
1999 to +9999
2 words:
19999999 to +99999999
0000 to 9999
F001 to F999
A000 to A999
[Display Type: DEC] (w/ sign , w/ sign +)
RS-232
RS-422
Setting
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422
4800 / 9600 / 19200 bps
7 / 8 bits
1 / 2 bits
None / Odd / Even
0 to 31
Transmission Mode 1 /
Transmission Mode 2
Indication on the V Series
0 to 9999
1 to 999
1000 to 1999
0 to 99999999
1 to 9999999
10000000 to 19999999
Upper: RS-232C
Lower: RS-422
13.1 PLC Connection
(Underlined setting: default)
Remarks
Transmission Mode 1: BCD without signs
Transmission Mode 2: BCD with signs
Setting
13-9