9. MITSUBISHI ELECTRIC
9.2.6
FR-E700
Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
CR/LF
Inverter
When setting run commands and set frequency commands from V9, select the Network operation mode. For more
information, refer to the Instruction Manual (Applied) of inverter.
Be sure to reset the inverter after making the initial settings of the parameters. Otherwise, communication is not possible.
Parameter
No.
77
Parameter writing permission
79
Operation mode selection
117
PU communication station number
118
PU communication speed
PU communication stop bit length
119
(data length)
120
PU communication parity check
121
Number of PU communication retries
122
PU communication check time interval
123
PU communication waiting time setting
124
PU communication CR/LF selection
Communication operation command
338
source
Communication speed command
339
source
Communication startup mode
340
selection
549
Protocol selection
NET mode operation command source
550
selection
PU mode operation command source
551
selection
Setting
1 : 1 / 1 : n / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
4800 / 9600 / 19200 bps
7 / 8 bits
1 / 2 bits
None / Odd / Even
0 to 31
None / CR / CRLF
Item
*3
*3
Setting
0: Writing allowed when PU operation
stops
1: Writing prohibited
2: Writing allowed during operation
0 / 1 / 2 / 3 / 4 / 6 / 7
0 to 31
4800 / 9600 / 19200 / 38400bps
0: 8 bits / 1 bit
1: 8 bits / 2 bits
10: 7 bits / 1 bit
11: 7 bits / 2 bits
0: None
1: Odd
2: Even
0 to 10 / 9999
*1
0
*2
0.1 to 999.8
9999
0 to 150 / 9999
0: Without CR/LF
1: With CR
2: With CR/LF
0: communication
1: external
0: communication
1: external (communication invalid)
2: external (communication valid)
0: As set in Pr.79
1: Network operation mode
*4
10: Network operation mode
0: Mitsubishi inverter protocol
1: Modbus-RTU protocol
0: communication option
2: PU connector
9999: Automatic communication option
recognition
2: PU connector
3: USB connector
4: Operation panel
9999: USB automatic recognition
(Underlined setting: default)
Remarks
(Underlined setting: default)
Setting Example
2
2 : External operation mode
0
19200 bps
1
2
9999:
The inverter does not stop even if a
communication alarm occurs.
9999: No communication check
9999: Can be set with the communication
data
1
0
0
1
0
9999
When using a communication option set
2.
9999