PLC
Make the PLC setting using the programming tool "GX-Developer". For more information, refer to the PLC manual issued by
the manufacturer.
Ethernet unit
PC parameter
Make the I/O assignment setting for the Ethernet unit.
Network parameter (Ethernet)
Item
Network type
Station I/O No.
Network No.
Group No.
Station No.
Ethernet operations
Item
Communication data code
Initial timing
IP address (DEC)
Enable Write at RUN time
Port No.
There are two types of ports: one is opened automatically by "auto-open UDP port" (default: 5000 DEC), and the other is
opened by open processing. When using the open processing, make settings for [Open settings] on the [Network
parameters] dialog. For more information, refer to the corresponding PLC manual.
Setting
Ethernet
Make settings in accordance with
the network environment.
Setting
Binary code
Always wait for OPEN (Communication
possible at STOP time)
Make settings in accordance with the
network environment.
Checked
9.1 PLC Connection
Remarks
For more information, refer to the manual of the PLC.
Remarks
It is not possible to write value from V9 to PLC when
unchecked.
If so, "error code received 7167" occurs.
9-19