12-2
12. M-SYSTEM
12.1.1 R1M Series
Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Remote I/O
Make PLC settings by using the software "R1CON". For more information, refer to the PLC manual issued by the manufacturer.
Modbus settings (RTU)
Item
Node Address
Baud Rate
Bit Length
Parity
Stop Bit
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
0
(output coil)
1
(input relay)
4
(holding register)
3
(input register)
Setting
1 : 1 / 1 : n / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
9600 / 19200 / 38400 bps

8 bits

1 / 2 bits
None / Odd / Even
1 to 15
Setting
1 to F H (= 1 to 15)
9600 / 19200 / 38400 bps
8 bits
NONE / ODD / EVEN
1 / 2 bits
Device Memory
Set by the address setting rotary switch.
TYPE
00H
01H
Read only
02H
03H
Read only
(Underlined setting: default)
Remarks
(Underlined setting: default)
Remarks
Remarks