9-46
9. MITSUBISHI ELECTRIC
Available Device Memory
The contents of "Available Device Memory" are the same as those described in "9.1.1 A Series Link".
When setting the device memory on the V-SFT, specify the station number as well.
Specify the network number using a macro. For more information, refer to the following.
Network specification macro
When accessing a PLC on a network number other than that directly connected via NET/10, execute "SYS (OUT_ENQ) F1" with the screen
open macro, and specify the network number to connect to.
Station numbers on multiple networks cannot be accessed from the same screen.
Macro command "SYS (OUT_ENQ) F1"
Contents
Network specification
Use this macro with the screen open macro. If used at any other time, a communication error will result since a network
change takes place immediately.
For more information on macros, refer to the separate Macro Reference manual.
Also refer to "network registration" in the "Standard Link / Multi-drop Link Unit" manual from Mitsubishi.
F0
n
n+1
OUT_ENQ
n+2
n+3
F1 (=$u n)
0 (fixed)
2 (fixed)
System code
1: NET/10
2: NET II (/B)
Network No. (fixed to 0 when n+2=2)