IP Address Setting of the V9 Series
An IP address must be set for the V9 to connect to devices via Ethernet. Set the IP address either on the V9 unit or for the
screen program using the V-SFT editor.
Setting Using the V-SFT Editor
Set the IP address at [System Setting]  [Hardware Setting]  [Local Port IP Address].
Local port IP address setting
Item
Select IP Address from
Network Table
*1
IP Address
*1
Default Gateway
*1
Subnet Mask
*1
Port No.
Item
These settings are valid when [1 : 1] is selected for [Connection Mode].
Select the IP address of the PLC registered in the PLC table. 1 : 1 communications are
executed with the PLC selected here.
Connect To
Click [Setting] to display the [PLC Table] window.
Set the IP address, port number and KeepAlive function (under development) of the
PLC.
PLC Table
This is valid when the IP address of the V9 has been registered in the network table.
Select a network table number from 0 to 255 to set the IP address.
* For more information on the network table, refer to " Network table" (page 1-50).
Set the IP address for the V9.
Set the default gateway.
Set the subnet mask.
When this box is not checked, the subnet mask is automatically assigned based on the byte at the extreme
left of the IP address.
Example:
When IP address is "172.16.200.185", "255.255.0.0" is set.
When IP address is "192.168.1.185", "255.255.255.0" is set.
Set a port number from 1024 to 65535.
(Excluding 8001 and 8020)