PLC_CTL
Macro command "PLC_CTL F0 F1 F2"
Contents
Read controller status
Operation instructions
Readout of main unit's
attribute
*1
8000 (HEX): broadcasting
13.2 Temperature Controller/Servo/Inverter Connection
F0
n
Station number
n + 1
Command: 0006H
Operation status (higher byte)
00: Control not in execution
01: Control in execution
1 - 8
(PLC1 - 8)
Related information (lower byte)
n + 2
Beyond the display range
n
Station number
n + 1
Command: 0030H
Communication writing
0000H: Communication writing OFF (disabled)
0001H: Communication writing ON (enabled)
Control start/stop
0100H: Channel 1 RUN
0101H: Channel 1 STOP
AT execution/cancel
0300H: AT cancel
0301H: AT execution at 100%
0302H: AT execution at 40%
Write mode
0400H: Backup mode
0401H: RAM write mode
0500H: Save RAM data
0600H: Software reset
0700H: Shift to set area 1
0800H: Protection level shift
Auto/manual
0900H: Auto mode
1 - 8
0901H: Manual mode
(PLC1 - 8)
0B00H: Initialize
n + 2
Alarm latch cancel
0C00H: Alarm latch 1 cancel
0C01H: Alarm latch 2 cancel
0C02H: Alarm latch 3 cancel
0C03H: Heater disconnection latch cancel
0C04H: SSR failure latch cancel
0C05H: Heater overcurrent latch cancel
0C0FH: All latch cancel
SP mode
0D00H: Program SP mode
0D01H: Remote SP mode
0D02H: Constant value control SP mode
Invert direct/reverse operation
0E00H: Not invert
0E01H: Invert
Infrared communication
1200H: OFF
1201H: ON
Hold
1300H: Hold cancel
1301H: Hold
1400H: Advance
n
Station number
n + 1
Command: 0005H
1 - 8
n + 2 -
Type (CHAR)
(PLC1 - 8)
n + 6
n + 8
Buffer size (HEX)
F1 (= $u n)
(Setting area 1, outputting manipulated variables for manual
operation, resetting operation or alarm occurrence)
(Other than above)
Bit
-
7 6 5 4 3 2 1 0
Potentiometer error
Input error
*1
* Data following 11th byte or later is
discarded.
Response code: Data stored from temperature controller to V series
13-41
F2
2
Heater overcurrent (CT1)
Heater current hold (CT1)
A/D converter error
Heater overcurrent (CT2)
Heater current hold (CT2)
3
2