8-6
8. LS
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
M
(internal memory)
Q
(output)
I
(input)
*1
The assigned device memory is expressed as shown
on the right when editing the screen.
Indirect Device Memory Designation
15
n+0
Model
n+1
n+2
Expansion code
n+3
 Using Q or I device memory
- Word access
QW1.7.3
Address number = A  32 + B  4 + C = 1  32 + 7  4 + 3 = 63
Specify "63" (DEC) for the address number.
- Bit access
QW1.7.63
Address number = A  32 + B  4 + (quotient of C divided by 16)
Bit designation = remainder when C is divided by 16 = (63  16) = 15
Specify "63" (DEC) for the address number, and "15" (DEC) for the bit designation.
Device Memory
8 7
Device type
Address No.
Bit designation
00
Station number
C (Address)
B (Slot No.)
A (Base No.)
C (Address)
B (Slot No.)
A (Base No.)
= 1  32 + 7  4 + (63  16) = 63
TYPE
00H
MW as word device
01H
*1
QW as word device
*1
02H
IW as word device
Example: Q 0 . 0 . 0
0
Remarks
Address
Period
Slot No.
Period
Base No.

Hide quick links: