8.1.11 XGT / XGI Series CPU

Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
PLC
No particular setting is necessary on the PLC.
Baud rate: 115200 bps, data length: 8 bits, without parity, stop bit: 1 bit (fixed)
Calendar
This model is equipped with a calendar function; however, the calendar data cannot be written from the V series. Thus, time
correction must be performed on the PLC side.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
M
(internal memory)
Q
(output)
I
(input)
R
(internal memory)
W
(internal memory)
F
(system flag)
K
(PID flag)
L
(link flag)
N
(P2P flag)
U
(analog data register)
*1
The assigned device memory is expressed as shown on the
right when editing the screen.
1 : 1 / Multi-link2 /
Multi-link2 (Ethernet)
115200 bps
Device Memory
Setting
RS-232C
8 bits
1 bit
None
TYPE
00H
MW as word device; MW0 to MW65535 valid
01H
QW as word device
*1
02H
IW as word device
03H
RW as word device
04H
WW as word device
05H
FW as word device; FW0 to FW1919: read only
06H
KW as word device
07H
LW as word device
08H
NW as word device
09H
UW as word device
Example: QW 0 . 0 . 0
8.1 PLC Connection
(Underlined setting: default)
Remarks
Remarks
*1
*1
Address
Period
Slot No.
Period
Base No.
8-15