Host Link Module (U-01DM)
Settings are the same as those described in " SU-5" (page 7-2).
SU-6H
Universal Communication Port
Set special registers "R772" and "R773", then specify "AA5A" (HEX) for the setting completion register "R767". When the set
value at R767 is changed to "AAAA" (HEX), it is regarded as normal; if it is changed to "AAEA" (HEX), it is regarded as erroneous.
Parameter setting register
Register
R772
R773
* Valid only when DIP switch No. 2 is set to OFF
DIP switch
The DIP switch provided at the rear of the CPU is used to make the following settings.
Switch
ON
Communication parameter settings can also be made by using the system parameter setting of the programmer. For more
information, refer to the PLC manual issued by the manufacturer.
Host Link Module (U-01DM)
Settings are the same as those described in " SU-5" (page 7-2).
0
0
E
0
Communication protocol
40: CCM
E0: Automatic recognition (Modbus, CCM, K-Sequence)
Communication timeout
0: 800 ms
Response delay time
0: 0 ms
8
7
0
1
Station number *
01 to 5A (HEX)
Baud rate
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
Parity stop bit
0: Without parity, stop bit 1
2: Without parity, stop bit 2
8: Odd parity, stop bit 1
A: Odd parity, stop bit 2
C: Even parity, stop bit 1
E: Even parity, stop bit 2
Item
No. 1
Battery mode
Station number
No. 2
setting
No. 3
No. 4
Setting
Setting
OFF: Without battery
ON:
With battery
OFF: According to the parameter setting
ON:
Fixed to 01
Invalid
7.1 PLC Connection
(Underlined setting: default)
Setting Example
00E0H
CCM
8701H
38400 bps
Odd parity
Stop bit 1
Station number 01
(Underlined setting: default)
Remarks
7-5