Fuji Electric Monitouch V9 Series Connection Manual page 255

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

9-62
9. MITSUBISHI ELECTRIC
9.2.2
FR-V500
Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
CR/LF
Inverter
Parameter
No.
77
Parameter writing permission
79
Operation mode selection
117
Communicating station number
118
Baud rate
119
Data length / stop bit length
120
Parity check
121
Communication retrial times
122
Communication check intervals
123
Wait time
124
CR/LF selection
146
Frequency setting
*1
When the value in the range from 0.1 to 999.8 is set:
If the V series does not start communication within the preset time, the inverter stops due to an alarm. This can be avoided by the
periodical reading setting.
*2
When the inverter is turned on with the settings of Pr.79=0 and Pr.146=9999, the inverter enters in the PU operation mode.
Setting
1 : 1 / 1 : n / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
4800 / 9600 / 19200 bps
7 / 8 bits
1 / 2 bits
None / Odd / Even
0 to 31
None / CR / CRLF
Item
0: Writing allowed when PU operation
stops
1: Writing prohibited
2: Writing allowed during operation
*2
0 / 1 / 2 / 3 / 4 / 6 / 7 / 8
0 to 31
4800 / 9600 / 19200 bps
0: 8 bits / 1 bit
1: 8 bits / 2 bits
10: 7 bits / 1 bit
11: 7 bits / 2 bits
0: None
1: Odd
2: Even
0 to 10 / 9999
*1
0 / 0.1 to 999.8 / 9999
0 to 150 / 9999
0: CR/LF not provided
1: CR provided, LF not provided
2: CR/LF provided
*2
0 / 1 / 9999
Remarks
Setting
2: Writing allowed during operation
1: PU operation
0
19200 bps
1: 8 bits / 2 bits
2: Even
9999:
The inverter does not stop even if a
communication alarm occurs.
9999: Communication check stop
9999: Can be set with the communication
data
1: CR provided, LF not provided
9999
(Underlined setting: default)
(Underlined setting: default)
Setting Example