7-4
7. KOYO ELECTRONICS
SU-5M/6M
Universal Communication Port 1
Set special registers "R772" and "R773", then specify "AA5A" (HEX) for the setting completion register "R767". When the set
value at R767 is changed to "AAAA" (HEX), it is regarded as normal; if it is changed to "AAEA" (HEX), it is regarded as erroneous.
Parameter setting register
Register
R772
R773
Communication parameter settings can also be made by using the system parameter setting of the programmer. For more
information, refer to the PLC manual issued by the manufacturer.
Universal Communication Port 2
Set special registers "R774" and "R775", then specify "A5AA" (HEX) for the setting completion register "R767". When the set
value at R767 is changed to "AAAA" (HEX), it is regarded as normal; if it is changed to "AEAA" (HEX), it is regarded as erroneous.
Parameter setting register
Register
R774
Same as the setting register R772 for the universal port 1
R775
Same as the setting register R773 for the universal port 1
Communication parameter settings can also be made by using the system parameter setting of the programmer. For more
information, refer to the PLC manual issued by the manufacturer.
Universal Communication Port 3
Set special registers "R776" and "R777", then specify "5AAA" (HEX) for the setting completion register "R767". When the set
value at R767 is changed to "AAAA" (HEX), it is regarded as normal; if it is changed to "EAAA" (HEX), it is regarded as
erroneous.
Parameter setting register
Register
R776
Same as the setting register R772 for the universal port 1
R777
Same as the setting register R773 for the universal port 1
Communication parameter settings can also be made by using the system parameter setting of the programmer. For more
information, refer to the PLC manual issued by the manufacturer.
0
0
E
0
Communication protocol
40: CCM
E0: Automatic recognition (Modbus, CCM, K-Sequence)
Communication timeout
0: 800 ms
Response delay time
0: 0 ms
8
7
0
1
Station number
01 to 5A (HEX)
Baud rate
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
Parity stop bit
0: Without parity, stop bit 1
2: Without parity, stop bit 2
8: Odd parity, stop bit 1
A: Odd parity, stop bit 2
C: Even parity, stop bit 1
E: Even parity, stop bit 2
Setting
Setting
Setting
(Underlined setting: default)
Setting Example
00E0H
CCM
8701H
38400 bps
Odd parity
Stop bit 1
Station number 01
Setting Example
00E0H
8701H
Setting Example
00E0H
8701H