13-6
13. OMRON
C500H-LK203
Back switch setting
Switch
5-V power supply
I/O port
Synchronization
Terminating resistance
CTS
SW1
SW2
C200HX / C200HG / C200HE
DIP switch
Item
SW5
C200HW-COM02 - 06
DIP switch
For the port A of C200HW-CCM03/06 (RS-422), the DIP switch setting is available.
DIP Switch
SW1
SW2
PLC system setting
Item
User Setting
Baud Rate
Parameter
Mode
Unit No.
Setting
OFF
Internal
Provided
0V
1 to 5
OFF
6
OFF
7
OFF
8
ON
1
OFF
2
OFF
3
ON
4
OFF
5
ON
6
OFF
7
ON
8
ON
Setting
ON
Standard setting
OFF
PC system setting
Change-over of 2-wire or 4-wire system
Terminator
Setting
Checked
4800 / 9600 / 19200
1, 7, 2, E
Host link
00
-
RS-232C/RS422
Applicable for RS-422
0 V
Unit No. 0
7 / 2 / even
Monitor
19200 bps
System No. 0
1 : n protocol
Disables levels 1, 2, and 3
7, 2, E, 9600 bps, Unit No. 0
Communication settings are made by setting DM6645 to 6648.
For more information, refer to the PLC manual issued by the
manufacturer.
Setting example
DM6645: "0001H"
DM6646: "0304H"
DM6648: "0000H"
Contents
The system setting can be made by specifying a value for the
address using a programming console.
For more information, refer to the PLC manual issued by the
manufacturer.
Contents
Remarks
Communication is performed according
to the setting for DM6646.
7, 2, E, 19200 bps
Unit No. 0
Setting
4 (4-wire system)
ON
Remarks

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents