PLC
Make the following settings on CX Programmer. For more information, refer to the PLC manual issued by the manufacturer.
Parameter setting
Item
IP Address
(FINS node address)
Subnet Mask
IP Address Conversion
FINS/UDP Port
Rotary switch
Switch
NODE No.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
DM
(data memory)
CH
(input/output/internal auxiliary relay)
H
(holding relay)
A
(auxiliary memory relay)
T
(timer/current value)
C
(counter/current value)
EMn
(extended data memory)
W
(internal relay)
TU
(timer/contact)
CU
(counter/contact)
*1
When using EMn (extended data memory), specify the bank number 0 to C (HEX).
The assigned device memory is expressed as shown on the right when editing the
screen.
Indirect Device Memory Designation
 EMn (extended data memory)
Specify the bank number 0 to C (HEX) in the expansion code.
IP address of the PLC
Set the same number as the node number of the rotary switch for the lowest byte which is to be the FINS
node address.
Subnet mask of the PLC
Automatic generation (dynamic)
Default (9600)
Set the FINS node number of the Ethernet unit.
Match the node number to the lower byte of the IP address.
Device Memory
Setting
Setting
TYPE
00H
01H
02H
04H
05H
06H
07H
*1
08H
09H
Read only
0AH
Read only
13.1 PLC Connection
Remarks
Example: EM0 : 30000
Address
Colon
Bank number
13-21