17-6
17. RS Automation
17.1.2 N7/NX Series (70/700/750/CCU)
Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Header
Monitor Registration
PLC
Be sure to match the settings to those made under [Communication Setting] of the editor.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
DT
(data register)
X
(external input)
Y
(external output)
R
(internal relay)
L
(link relay)
LD
(link register)
FL
(file register)
SV
(timer, counter/set value)
EV
(timer, counter/elapsed time)
T
(timer/contact)
C
(counter/contact)
1 : 1 / 1 : n / Multi-link / Multi-link2 /
Multi-link2 (Ethernet) / 1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
4800 / 9600 / 19200 / 38400 / 57600 / 76800 /
None / Odd / Even
% (Header) / < (Extension Header)
Unchecked / Checked
Device Memory
Setting
115K bps
7 / 8 bits
1 / 2 bits
0 to 31
TYPE
00H
01H
WX as word device, read only
02H
WY as word device
03H
WR as word device
04H
WL as word device
05H
06H
07H
08H
09H
Read only
0AH
Read only
(Underlined setting: default)
Remarks
Only port No. 31 is valid, depending on the CPU model.
For connection with a CCU module, select port No. 1.
Models on which "< (Expansion Header)" is available:
NX-CPU750A / NX-CPU750B / NX-CPU750C /
NX-CPU750D / NX70-CPU750
One V9 unit can be registered as a monitor for one PLC.
When multi-link connection (n : 1) is selected, do not
check this box for multiple V9 units.
Remarks