13.2.9 E5ZD
Communication Setting
Editor
Communication setting
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Temperature Controller
Switch
SW2
SW3
The following settings are fixed; data length: 7, stop bit: 2, and parity: even.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
0000 Control temperature
0001 Measurement temperature
0002 Operation status
0003 Output value
0004 Output value on the cooling side
0005 Proportional band
0006 Integral time
0007 Derivative time
0008 Control cycle
0009 Control cycle on the cooling side
000A Output operation
000B Heater disconnection effective channel
000C Alarm status
-
000D Warning mode: warning 1
000E Warning mode: warning 2
000F Temperature at which an alarm occurs:
warning 1
0010 Temperature at which an alarm occurs:
warning 2
0011 Execution memory bank No.
0012 Adjustment sensitivity
0013 Adjustment sensitivity on the cooling side
0015 Input offset value
001D Heater disconnection detection level
001F Heater current value
0021 Deadband / overlap band
0022 Cooling coefficient
Item
1 : 1 / 1 : n / Multi-link2 / Multi-link2 (Ethernet) /
Device Memory
13.2 Temperature Controller/Servo/Inverter Connection
Setting
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
4800 / 9600 bps
7 bits
2 bits
Even
0 to 15
Setting Data
Unit No.
Baud rate
TYPE
Bank No. 0
Bank No. 0
Bank No. 0
Bank No. 0
Bank No. 0
Bank No. 0
Bank No. 0
00H
Bank No. 0
Bank No. 0
Bank No. 0
Bank No. 0
Bank No. 0
13-43
(Underlined setting: default)
Remarks
(Underlined setting: default)
Setting
0 to F (= 0 to 15)
5: 4800 bps
6: 9600 bps
Remarks